CURENTI
MAXIMI ADMISIBILI IN REGIM PERMANENT LA CONDUCTOARE IZOLATE
Temperatura
mediului ambiant: + 250 C
Temperatura
maxima admisa pe conductor:
+ 700
C, la izolatie de PVC
+ 600
C, la izolatie de cauciuc
Sect. nominala
a cond.
[mm2
|
Intensitatile curentilor, A
|
Conductoare de cupru
cu izolatie de PVC sau de cauciuc FY, FcTi
|
Conductoare de
aluminiu cu izolatie de PVC sau cauciuc AFY
|
Montate in tub Nr.
conductoarelor in tub
|
Libere in aer
|
Montate in tub Nr.
conductoarelor in tub
|
Libere in aer
|
2
|
3
|
4
|
5,6
|
|
2
|
3
|
4
|
5,6
|
|
0
|
1
|
2
|
3
|
4
|
5
|
6
|
7
|
8
|
9
|
10
|
1
|
14
|
12
|
11
|
10
|
20
|
|
|
|
|
|
1,5
|
17
|
14
|
13
|
11
|
25
|
|
|
|
|
|
2,5
|
24
|
20
|
18
|
16
|
34
|
18
|
16
|
15
|
13
|
27
|
4
|
31
|
26
|
24
|
21
|
45
|
23
|
20
|
18
|
16
|
35
|
6
|
40
|
34
|
31
|
27
|
57
|
30
|
27
|
25
|
21
|
45
|
10
|
55
|
49
|
45
|
39
|
78
|
41
|
38
|
33
|
29
|
61
|
16
|
73
|
64
|
58
|
51
|
104
|
55
|
47
|
43
|
38
|
82
|
25
|
100
|
84
|
76
|
67
|
137
|
74
|
66
|
60
|
53
|
107
|
35
|
125
|
108
|
98
|
87
|
168
|
95
|
83
|
76
|
65
|
132
|
50
|
150
|
135
|
123
|
109
|
210
|
118
|
103
|
94
|
82
|
165
|
70
|
200
|
171
|
156
|
137
|
260
|
155
|
131
|
119
|
104
|
205
|
95
|
241
|
218
|
198
|
174
|
310
|
187
|
166
|
151
|
133
|
245
|
120
|
272
|
250
|
228
|
196
|
365
|
217
|
191
|
174
|
153
|
285
|
150
|
310
|
280
|
255
|
224
|
415
|
238
|
214
|
195
|
171
|
330
|
185
|
|
|
|
|
475
|
|
|
|
|
375
|
240
|
|
|
|
|
560
|
|
|
|
|
440
|
300
|
|
|
|
|
645
|
|
|
|
|
510
|
400
|
|
|
|
|
750
|
|
|
|
|
605
|
OBSERVATII:
1.
Intensitatile curentilor pentru trei conductoare in tub sunt
valabile si pentru circuite trifazate (echilibrate sau nu) cu patru sau
cinci conductoare (3L + N, 3L + N + PE).
2. Pentru
conducte punte cu doua conductoare, respectiv trei conductoare, se
folosesc valorile intensitatilor date pentru doua conducte,
respectiv trei conducte in tub.